HIO (Operator Interfaces with I/O)


 • All features of Prizm LCD Operator Interfaces 
 • Integrated Digital Inputs and Outputs with optional Analog I/O
 • Digital Inputs and Outputs rated for 24 V DC
 • Analog Inputs for RTD, Thermocouple, mV and mA.
 • Analog Outputs are 4-20 mA
 • Inputs connectable to PLC or used for internal program
 • Support for simple ladder logic and analog control
 • Support for high speed counters and timer
 • Dual Port Support for connecting to a PLC / Printer / SCADA / Drive
 • Common Programming software for the entire HIO family.........FREE!!
 • IP65 design. CE and UL certified

See Our Specials Page

Download Information Sheet

Download The Software (it is free!)


Specifications:

Power + 24V DC ± 10%
Bezel Bezel IP 65 rated keypad
Operating Temp 0o to 50o C
Storage Temp -20o to 80o C
Humidity 10% to 90% (Non-condensing)
Communication Two communication ports. (User configurable)
Immunity to ESD Level 3 as per IEC1000-4-2
Immunity to Transients Level 3 as per IEC1000-4-4
Immunity to Radiated RF Level 3 as per IEC1000-4-3
Emission EN55011 CISPR A
Universal Analog Inputs: Software Selectable
 

0-100 mV, 0-50 mV
0-20 mA, 4-20 mA
3-wire RTD (Alpha1, Alpha2)
Type B, R, S, E, J, K, N and T
Analog Outputs:
mA

4-20 mA
Digital Inputs:
Rated Input Voltage
Rated Input Current
Minimum ON Voltage
Minimum OFF Voltage

24V DC
10mA
10V
3.0V
Digital Outputs:
Maximum Load current
Voltage drop at ON
Maximum Reverse Voltage
50mA
0.4V or less
6V Digital
Outputs (Relay):
Ralay Rating
 
230V AC, 2 Amp. (max.)

                  
                  





  
 

Programmability
The HIO unit possess both Prizm (Operator interface) as well as programmable logic features. User can implement logic, specific to application using standard Ladder programming. The HIO unit has four High speed counters (5 K Hz.), hundreds of timers and counters, thousands of internal coils, retentive and nonretentive memory and PID functionality. A programming logic task can be programmed for continuous scanning, or only when a specific screen is showing. User can also include Programmable logic task in power on as well as Global task. The HIO operator interface functions revolve around Screens and Tasks that can be assigned to keys, screens and application. The HIO can also display an Alarm condition.

Supported Tasks are listed below:


 
1. Go to Screen
2. Go to Next Screen
3. Go to Previous Screen
4. Write Value to a Tag
5. Add a Constant to Tag
6. Subtract a Constant from Tag
7. Add Tag B to Tag A
8. Subtract Tag B from Tag A
9. Turn Bit On
10. Turn Bit Off
11. Toggle Bit
12. Copy Tag B to Tag A
13. Swap Tag A and Tag B
14. Print Data
15. Set RTC
16. Copy Tag to STR
17. Copy Tag to LED
18. Delay
19. Wait
20. Copy Recipe Blk to PLC Blk
21. Copy PLC Blk to Recipe Blk
22. Execute PLC Logic Block.

Digital I/O
The HIO series can have up to 16 digital inputs and up to 12 digital outputs. Digital inputs are high impedence 24 V DC and outputs are either relay (Only NO), open collector or combination of both.

Analog I/O
HIO series supports up to 4 analog inputs and up to 2 analog outputs. Analog inputs are 4-20mA, mV, Thermocouple and RTD. Analog outputs are 4-20 mA.

Keys Tasks
Keys in HIO can be assigned Tasks for three instances: when key is pressed once, while key is pressed and when key is released. Multiple tasks can be assigned to a key. Tasks can be assigned to a combination of two keys. Also different screens can have different key definitions. Keys can have password protection. In addition to above-mentioned tasks, Key’s specific tasks can be defined for keys. These include tasks for data entry, alarm management etc. These definitions allow complete flexibility in cursor control and key operations when changing data.

Screens
Up to 65535 screens can be defined in HIO. Screen Tasks can be assigned before showing a screen, while showing a screen and after hiding a screen. Various types of objects can be defined on the screen. Objects include plain text objects, Data display (coil status, register value, register dependent text), Data entry objects, Alarm objects. Two screens can be associated to avoid duplication of screens and objects.

Data entry objects can have limits and math associated. Various types of data formats are available which help user to edit data easily. Float data entry is also possible.

Alarms
Up to 256 alarms (16 for text models) can be defined in HIO.
Alarms can either be consecutive or discrete. User-friendly alarm object can be defined on the display. Optional Alarm logging along with on / off timers is also available. Keys can be assigned to acknowledge alarm, print alarm, view next / previous alarm etc.

Dual Port Support
HIO units have two communication ports. Both the ports can be configured as RS232, RS485 / RS422. Both the COM ports can also be defined as programming port or to connect a Printer / PLC / SCADA / Drive etc. Drivers can be downloaded in HIO units for Dual Port application

Configuration Software
HIO unit has to be configured before its use in any system.

Complete configuration consists of defining:
1. HIO Settings
2. PLC node
3. Tag Database
4. Global Keys
5. Alarms
6. Global and Power-on Task list
7. Screens and Screens Task-List, Screen keys, if required.

The complete configuration is stored as an Application. This application is downloaded in HIO.

Prizm32 is a compact, Windows® based software to configure the HIO Series Interfaces. Prizm32’s tools and easy approach can help you create your applications quickly and easily. By using some of Prizm32’s new features, you can be more effective in what you need. Whether you need a small application to monitor data or a bigger application for both monitoring and changing data in your PLC, Prizm32 has it all.

With Prizm32 you can get started quickly to use your Prizm Interfaces.

HIO user should follow the given procedure to configure and use HIO units:
1. Create an application
2. Connect IBM cable
3. Download Firmware
4. Download application.

Other Items required for HIO configuration
1. HIO unit
2. Prizm32
3. IBM Cable (Part codes: IBM 0909-1 or IBM 0925-1)

System requirements for Prizm32 are:
Windows Version : Microsoft Windows® NT / 2000 / XP
Processor : PENTIUM or higher
Mouse : Required
RAM : 64 MB or more
Display resolution : 800 x 600 (VGA) or better
Display colors : 256 colors or more

 
Model Display Digital Inputs Digital Outputs Analog Inputs Analog Outputs Dimensions Part Number
HIO005
128 x 64 px. (1.25” g*)
6
6
1
1
48 x 48 x 76
HIO005-0606-0101-U-B-C-00
HIO050
20 x 4 (Text)
16
12
4
2
183 x 101 x 37
HIO050-1612-0402-U-B-C-00
HIO140
128 x 64 px.
(3” Graphical)
16
12
4
2
183 x 101 x 37
HIO140-1612-0402-U-B-R-00
HIO230
192 X 64 px.
(4.1” Graphical)
16
12
4
0
140 x 77 x 35
HIO230-1612-0400-U-B-C-00-S2

The models shown above and in the purchase section are the ones we normally hold in stock. The information sheet shows are models. If you require a model not normally stocked please contact us for a price. Delivery for non stocked items is normally 3 to 4 weeks

Download Information Sheet